Good day! In today's article, we will discuss the topic of temperature reflection of buildings, the results of measurements of the temperature of the internal air and the temperature of the inner surface of the outer wall, on the outer surface of which the Bronya heat insulator was applied
Measured objects |
Temp., [оС] |
Rad., |
Ref., temp., [оС] |
Notes |
Measuring point 1 |
16,8 |
0,95 |
20,0 |
Does not exceed normative |
Measuring point 2 |
20,0 |
0,95 |
20,0 |
Does not exceed normative |
As a result of the measurements, the temperature on the inner surface of the building envelope was determined. On the outside of which the Bronya heat insulator is applied and without additional thermal insulation.
According to SNiP 23-03-2003 “Thermal protection of buildings”, the standardized temperature difference between the temperature of the internal air and the temperature of the internal surface must not exceed the values given in the table.
The difference between the temperature of the internal air and the temperature of the inner surface of the outer wall, on the outer surface of which the Bronya heat insulator was applied, is 3.2 ° C, which does not exceed the normalized temperature difference for external walls of 4 ° C.
The difference between the temperature of the internal air and the temperature on the surface of the inner wall is not standardized and is 0 ° C.
Measured objects |
Temp., [оС] |
Rad., |
Ref., temp., [оС] |
Notes |
Measuring point 1 |
10,6 |
0,95 |
19,0 |
Exceeds normative |
Measuring point 2 |
16,9 |
0,95 |
19,0 |
Does not exceed normative |
According to SNiP 23-03-2003 “Thermal protection of buildings”, the standardized temperature difference between the temperature of the internal air and the temperature of the internal surface must not exceed the values given in the table. The difference between the temperature of the internal air and the temperature of the inner surface of the outer wall, on the outer surface of which the Bronya heat insulator was applied, is 3.1 ° C-1.8 ° C, which does not exceed the normalized temperature difference for external walls of 4 ° C. The difference between the temperature of the internal air and the temperature of the inner surface of the outer wall, on the outer surface of which the Bronya heat insulator was applied, is 9.4 ° C, which does not exceed the normalized temperature difference for external walls of 4 ° C.